DC4xD MK3 GENSET CONTROLLER USER MANUAL
9
Descriptions of terminal connection
No.
Function
Description
Cable
cross
sectional
area
1
Battery Negative Input B-
Controller power supply input B-.
2.5mm
2
2
Battery Negative Input B+
Controller power supply input B+.
2.5mm
2
3
Emergency Stop Input
B+ voltage input is active, and connected
to emergency stop normal closed button.
2.5mm
2
4
Fuel Output
+VE output, Max 16Amp
1.5mm
2
5
Crank Output
+VE output, Max 16Amp.
1.5mm
2
6
AUX. OUTPUT1
+VE output, Max 5Amp.
1.5mm
2
7
AUX. OUTPUT2
+VE output, Max 5Amp.
1.5mm
2
8
AUX. OUTPUT3 Normal open
Passive Output, Max 5Amp
1.5mm
2
9
AUX. OUTPUT3 Normal open
1.5mm
2
10
AUX. OUTPUT4 Normal open
Passive Output, Max 5Amp
1.5mm
2