If setting as warning,the AUX. INPUT
should be set as Low oil pressure stop
disabled and input is valid. When the oil
pressure value is lower than the preset
value or low oil pressure alarm input
signal is valid, then controller only
display warning but not stop.
Alarm and stop: when the temperature
is higher than preset value or high
temperature signal is valid, then
controller will alarm and stop after
normal faults delay.
If setting as warning:the AUX. INPUT
should be set as high temperature stop
disabled and input is valid. When the
temperature value is higher than the
preset value or high temperature alarm
input signal is valid, then controller only
display warning but not stop.
If setting as alarm and stop after
unloading:the AUX. INPUT should be
set as high temperature stop and input
is valid. When the temperature value is
higher than the preset value or high
temperature alarm input signal is valid,
then controller shall start the unloading
procession and stop with alarm.