DC5xD MK3 GENSET CONTROLLER USER MANUAL
40
3 Phase 3 Wire
3 Phase 4 Wire
When the mains voltage is lower than the "low
voltage crank threshold" and comes into mains
low voltage delay(normal failure delay) but still
lower, then mains becomes invalid. If the voltage
become higher than "low voltage revert threshold"
during normal failure delay time, then it will not
alarm.
When the mains voltage is higher than the" high
voltage crank threshold" and comes into mains
high voltage delay(normal failure delay) but still
higher, then mains becomes invalid. If the voltage
become lower than "low voltage revert threshold"
during normal failure delay time, then it will not
alarm.
The time from abnormal to normal, which is used
for ATS transfer.
9) LCD setting
Start screen display time,0: No-display.
LCD light will be closed automatically without
any button pressed after delay.If setting as
200.0s, back light always lighted.
The time when the page reverts back to the
home page .If setting as 600.0s:disabled.
LOGO delay display
under standby
Start screen will be opened without any button
pressed after delay.If setting as 6000.0s:
disabled.
Set the LCD display contrast.
a) USB/RS485 PORT
The IP built by controller and PC.
0-4800
1-9600
2-19200
3-38400
4-57600
5-115200
RS485 communication baud rate.
RS485 communication CRC correction high and
low bits
b) Working plan
Disable
Enable 1:remote start
Enable 2:mains failure
Enable 3:the above 1 or 2
Enable 4:running always
Working plan must be under auto mode.During
the working time, the genset start if the
conditions reached and shall stop if the
conditions not reached.
The genset shall not start when out of the