M
AVTMDELTA4000-EN Rev 6 April 2018
8
>100 mA, continuous output
>300 mA, up to 4 minutes
The output current capacity can be expanded to 4 A
using the optional Resonating Inductor, catalog number
670600-1
25 V to 12 kV, 1 V maximum resolution
0 to 5 A, 0.1 A maximum resolution
The measurement can be corrected to either 2.5 kV or
10 kV equivalents
0 to 100 F, 0.01 pF maximum resolution
6H to 10MH, 0.1 mH maximum resolution
0 to 100%, 0.001% maximum resolution
0 to 100, 0.001% maximum resolution
0 to 2 kW, actual power, 0 to 100 kW when corrected to
10 kV equivalent. 0.1mW maximum resolution.
The measurement can be corrected to either 2.5 kV or
10 kV equivalents.
Individual temperature correction (ITC) from 5°C to
50°C test temperature to 20°C reference, (using Power
DB)
Standard tables for temperature corrections
±(0.5% of reading + 1 pF)
±(0.5% of reading + 1 mH)
±(0.5% of reading + 0.02%)
±(0.5% of reading + 0.02%)