-23 -
4. Technician settings (cont’)
P13 – Door switch / Door key-tag delay time
Range: 0…999 seconds
Default: 180 seconds
P14 – Enable/Disable Auto change over mode
“00” - Disable Auto change over mode
“01” - Enable Auto change over mode (default)
P15 – Occupancy sensor logic (PIR)
“00” - Thermostat turns off when unoccupied
and back on when re-occupied
“01” - Thermostat turns off when unoccupied
and remains off when re-occupied
“02” - Thermostat uses economy set points (default)
P12 Polarity of door switch/key-tag contact on terminals T1,0
(P08 = “03” or “04”)
“00” - Normally close (default)
“01” - Normally open
P10 Polarity of remote switch contact on terminals IN,0
(P09 = “03” or “04”)
“00” - Normally close (default)
“01” - Normally open
P11 – Time delay of remote switch contact on terminals IN,0
(P09 = “03” or “04”)
Range: 0…999 seconds.
Default: 600 seconds.