Temperature
Time
Normal work Freeze protection
Cut-in
Cut-out
The Freeze protection feature will not allow the room temperature to
drop below predefined cut-in temperature. Depending on which
configuration the system is operating under (with or without Heat pump)
this feature will force the system to operate in heat mode and activate
the fan.
This feature will take effect when the thermostat is either ON or OFF.
When the room temperature rises above the predefined cut-out
temperature, the thermostat will return to its previous state.
When freeze protection is activated, the display alternates between
“AL” and room temperature.
For selection of cut-in and cut-out temperatures, please refer to
technician settings parameters P36 and P37.
-9 -
1.11 Freeze protection