4. Technician settings (cont’)
-25 -
P30 – Beeper ON or OFF
“01” - Beeper ON (default)
“00” - Beeper OFF
P31 – Fan ON delay in cooling (seconds) (FC only!)
Range: 0…120 seconds
Default: 0 seconds (no delay)
P32 – Fan OFF delay in cooling (seconds)
Range: 0…120 seconds
Default: 0 seconds (no delay)
P33 – Fan ON delay in heating (seconds) (FC only!)
Range: 0…120 seconds
Default: 0 seconds (no delay)
P34 – Fan OFF delay in heating (seconds)
Range: 0…120 seconds
Default: 30 seconds
P27 – Time on-delay between heating stages
Range: 0…600 seconds
Default: 5 seconds
P28 – Time off-delay between heating stages
Range: 0…600 seconds
Default: 1 seconds