4. Technician settings (cont’)
-29 -
P55 – Heat proportional band (FC only!)
Range: 2...10°C / 4…20°F
Default: 2°C / 4°F
P56 – Heat proportional low limit (FC only!)
Range: 0...100%
Default: 0%
P57 – Heat proportional high limit (FC only!)
Range: 0...100%
Default: 100%
P60 – Proportional ON percent (FC only!)
Range: 0...30%
Default: 30%
P61 – Proportional OFF percent (FC only!)
Range: 0...20%
Default: 10%