440 & 450 ELECTRONIC VIBRATION SWITCHES
Installaon Manual
1. OVERVIEW
1.1 Introducon
The single setpoint models (SR) contain one
trip limit for shutdown. The oponal dual
setpoint models (DR) contain two indepen-
dent trip limits; one for alarm and one for
shutdown. Shutdown and alarm limits are
in engineering units of velocity. In addion,
a 4-20 mA output proporonal to vibraon
velocity is provided.
Models 440 and 450 use idencal design
and dier only in the enclosure. The model
440 is designed to be used in non-hazardous
or non-incendive hazardous locaon (Class
I, Division 2, Groups B, C, D, and NEMA
4X). The model 450 is designed to meet
explosion-proof requirements for Class
I, Division 1, Groups B, C, D installaons.
Unless otherwise noted, all discussions and
diagrams herein assume the model 440, but
apply equally to the model 450.
1.2 KeyCapabilies
Shutdown and alarm sengs are based
on vibraon severity. The internal sen-
sor (unless the external sensor opon
has been specied (Ordering Opon
I=5 – see note in Secon 5.4) is a piezo-
electric crystal with built in microelec-
tronics to reduce noise sensivity. The
output signal is electronically integrat-
ed to measure and trip on velocity.
Calibrated setpoint controls permit set-
point adjustment of vibraon velocity
levels up to full scale range. DR model
Doc# 90018-031 • REV L (April 2016)