27
OM 1364
WWW.DAIKINAPPLIED.COM
DEHUMIDIFICATION
Wiring
Figure 14: Thermostat and sensor combination hot gas
reheat smart dehumidication wiring diagram
R
Y2
C
G
Y1
Unit
HST
I/O Exp Board
R 24VAC
Cool Stage 2
Y2
Common
C
FanG
Cool Stage 1Y1
Thermostat
R 24VAC
Dehumid
DH
Humidistat
Figure 15: Thermostat and sensor combination hot gas
reheat smart dehumidication wiring diagram
R
C
G
Y1
Unit
HST
I/O Exp Board
R 24VAC
Common
C
FanG
Cool Stage 1Y1
Thermostat
R 24VAC
Dehumid
DH
Humidistat
Operation
A call for heating or cooling has a higher priority than a call for
dehumidication. Dehumidication is allowed only if the room
temperature is satised and the return air temperature is 68°F or
greater. If the controller detects the need for heating or cooling,
or if the Humidistat is no longer calling for dehumidication,
dehumidication mode will be suspended. Dehumidication
mode will enable the 3-way hot gas bypass valve, sending hot
superheated refrigerant to the hot gas reheat coil while running
the compressor at full load and the fan at dehumidication speed.
NOTICE
See Fan Performance section in catalog for unit size specic fan speeds.
Figure 16: Unit with WSE and HGR thermostat Wiring
Diagram
R 24VACR
Cool Stage 2
Y2Y2
W4
Common
CC
Fan
GG
Cool Stage 1
Y1
Cool Stage 3
Y3
Y1
Unit Thermostat
R 24VAC
Dehumid
DH
Humidistat
HST
I/O Exp Board