EasyManua.ls Logo

Midea Aqua Tempto Power Series

Midea Aqua Tempto Power Series
213 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
140
1.2 MGBT-F60W/RN1
No
Code
Trouble
1
E0
Water flow detection error (The third time)
2
E1
Power phase sequence error
3
E2
Communication error
4
E3
Total water outlet temp. sensor error
5
E4
Outlet water temp. sensor error in shell and tube heat exchanger
6
E5
Pipe temp. sensor error in condenser A
7
E6
Pipe temp. sensor error in condenser B
8
E7
Outdoor ambient temp. sensor error or power supply protection
9
E8
(Reserved failure code)
10
E9
Water flow detection error (The first and second times)
11
EA
Main unit detected that auxiliary unit’s quantity have decreased.
12
Eb
Freeze-proof temp. sensor 1 error in double-pipe heat exchanger
13
EC
Wired controller did not find out any on-line module unit.
14
Ed
1-hour consecutive 4-times PE protection happens
15
EF
Inlet water temp. sensor error
16
P0
High pressure or air discharge temp. protection error in system A
17
P1
Low pressure protection happens to system A
18
P2
High pressure or air discharge temp. protection in system B
19
P3
Low pressure protection happens to system B
20
P4
Current protection happens to system A
21
P5
Current protection happens to system B
22
P6
Condenser high pressure protection in system A
23
P7
Condenser high pressure protection in system B
24
P8
Air discharge temp. sensor protection of digital compressor in ystem A
25
P9
Protection of outlet and inlet water temp. difference
26
PA
Low ambient temp. drive-up protection
27
Pb
System freeze-proof protection
28
PC
(Reserved failure code)
29
PE
Low temp. protection of double-pipe heat exchanger
30
F1
Wired controller failure
31
F2
(Reserved failure code)

Table of Contents

Related product manuals