EasyManua.ls Logo

Midea AURORA ONOFF Series - E2;EH 02 (Zero-Crossing Detection Error Diagnosis and Solution)

Midea AURORA ONOFF Series
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting 15
7.2 E2/EH 02 (Zero crossing detection error diagnosis and solution)
Description: When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time
interval is abnormal.
Recommended parts to prepare:
Connection wires
Indoor PCB
Troubleshooting and repair:
Check the connections and
power supply.
Correct the connections. Turn on the
unit when the power supply is good.
NO
Indoor main PCB is defective. Replace
indoor main PCB.
YES
Is it normal?
Note: E2 zero crossing detection error is only valid for the unit with AC fan motor, for other models, this error
is invalid.

Table of Contents

Related product manuals