Midea AC Fan Coil Unit
14
(Continued)
MKH2(3)-350-R4
EWT
ΔT
Indoor
temp
(W.B.)
Indoor temperature (D.B.)
21
23
25
27
29
TC
SC
WF
WPD
TC
SC
WF
WPD
TC
SC
WF
WPD
TC
SC
WF
WPD
TC
SC
WF
WPD
°C
°C
°C
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
11
3
15
1.62
1.62
0.47
11.49
2
2
0.58
16.47
2.37
2.37
0.68
22.1
2.73
2.73
0.78
27.8
3.08
3.08
0.89
34.74
17
2.21
1.59
0.63
19.31
2.27
1.98
0.66
20.5
2.42
2.37
0.7
22.81
2.73
2.73
0.78
27.9
3.09
3.09
0.89
34.87
19
3.45
1.63
1
42.12
3.42
1.99
0.99
41.54
3.39
2.35
0.98
40.97
3.37
2.71
0.98
40.54
3.4
3.07
0.98
41.15
20
-
-
-
-
4.04
2.01
1.16
54.96
4.01
2.36
1.15
54.2
3.98
2.72
1.15
53.5
3.95
3.06
1.14
52.75
4
15
1.5
1.5
0.32
6.11
1.89
1.89
0.41
9.13
2.27
2.27
0.49
12.37
2.64
2.64
0.57
15.97
2.99
2.99
0.65
20.05
17
1.85
1.44
0.4
8.78
2.04
1.86
0.44
10.38
2.29
2.27
0.49
12.51
2.65
2.65
0.57
16.02
3
3
0.65
20.12
19
3.12
1.5
0.67
21.41
3.09
1.86
0.67
21.12
3.07
2.23
0.67
20.89
3.11
2.6
0.67
21.37
3.23
3
0.69
22.58
20
-
-
-
-
3.75
1.89
0.81
29.44
3.72
2.25
0.81
29.06
3.69
2.6
0.8
28.65
3.69
2.96
0.8
28.64
5
15
1.25
1.25
0.22
2.69
1.76
1.76
0.3
5.54
2.16
2.16
0.37
7.8
2.54
2.54
0.44
10.26
2.9
2.9
0.5
12.9
17
1.46
1.26
0.25
3.9
1.83
1.75
0.31
5.87
2.16
2.16
0.37
7.82
2.54
2.54
0.44
10.29
2.91
2.91
0.5
12.95
19
2.69
1.33
0.46
11.28
2.67
1.7
0.46
11.11
2.73
2.08
0.47
11.62
2.87
2.49
0.49
12.58
3.04
2.89
0.53
13.95
20
-
-
-
-
3.38
1.74
0.58
16.69
3.35
2.1
0.58
16.44
3.36
2.47
0.58
16.51
3.44
2.86
0.59
17.14
6
15
0.95
0.95
0.14
1.16
1.52
1.52
0.22
2.73
2.02
2.02
0.29
5.11
2.42
2.42
0.35
6.91
2.8
2.8
0.4
8.83
17
0.95
0.95
0.14
1.17
1.52
1.52
0.22
2.74
2.02
2.02
0.29
5.12
2.42
2.42
0.35
6.94
2.8
2.8
0.4
8.86
19
2.04
1.08
0.29
5.16
2.18
1.51
0.31
5.78
2.4
1.95
0.34
6.76
2.63
2.37
0.38
7.92
2.87
2.78
0.41
9.26
20
-
-
-
-
2.89
1.55
0.42
9.3
2.91
1.94
0.42
9.4
3.03
2.34
0.43
10.04
3.18
2.73
0.46
10.93
13
3
15
1.23
1.23
0.36
7.13
1.62
1.62
0.47
11.35
1.99
1.99
0.58
16.15
2.36
2.36
0.68
21.54
2.72
2.72
0.78
27.07
17
1.31
1.21
0.38
7.95
1.63
1.62
0.47
11.33
2
2
0.58
16.21
2.37
2.37
0.68
21.61
2.72
2.72
0.78
27.17
19
2.41
1.22
0.7
22.26
2.38
1.58
0.69
21.84
2.41
1.96
0.7
22.29
2.52
2.35
0.72
23.67
2.73
2.72
0.78
27.22
20
-
-
-
-
3.04
1.61
0.87
32.86
3.02
1.97
0.86
32.37
3
2.33
0.86
32.13
3.05
2.7
0.87
32.98
4
15
1.04
1.04
0.22
3.02
1.5
1.5
0.32
6.08
1.89
1.89
0.41
8.98
2.27
2.27
0.49
12.09
2.63
2.63
0.56
15.58
17
1.05
1.05
0.23
3.08
1.51
1.5
0.32
6.08
1.9
1.9
0.41
9.01
2.27
2.27
0.49
12.13
2.64
2.64
0.57
15.64
19
1.93
1.04
0.42
9.25
1.95
1.4
0.43
9.87
2.15
1.85
0.46
11.09
2.35
2.25
0.5
12.82
2.64
2.63
0.57
15.66
20
-
-
-
-
2.65
1.46
0.57
15.75
2.64
1.83
0.57
15.67
2.72
2.22
0.58
16.43
2.84
2.61
0.61
17.79
5
15
0.73
0.73
0.13
1.02
1.3
1.3
0.22
2.97
1.76
1.76
0.3
5.41
2.15
2.15
0.37
7.58
2.53
2.53
0.43
9.95
17
0.73
0.73
0.13
1.02
1.3
1.3
0.22
2.99
1.77
1.77
0.3
5.42
2.16
2.16
0.37
7.61
2.53
2.53
0.44
9.98
19
0.81
0.64
0.14
1.17
1.58
1.27
0.27
4.49
1.89
1.72
0.32
6.06
2.19
2.16
0.38
7.79
2.54
2.54
0.44
10.01
20
-
-
-
-
2.11
1.27
0.36
7.29
2.26
1.69
0.39
8.14
2.45
2.1
0.42
9.33
2.67
2.52
0.46
10.83
6
15
0.6
0.6
0.09
0.68
0.95
0.95
0.14
1.12
1.57
1.57
0.22
2.97
2.03
2.03
0.29
5.04
2.42
2.42
0.35
6.79
17
0.6
0.6
0.09
0.68
0.95
0.95
0.14
1.12
1.58
1.58
0.22
2.99
2.03
2.03
0.29
5.06
2.42
2.42
0.35
6.82
19
0.63
0.55
0.09
0.7
0.96
0.94
0.14
1.13
1.61
1.58
0.23
3.23
2.04
2.03
0.29
5.09
2.43
2.43
0.35
6.84
20
-
-
-
-
1.05
0.87
0.15
1.3
1.87
1.53
0.27
4.35
2.19
1.98
0.31
5.74
2.49
2.4
0.36
7.12
15
3
15
0.8
0.8
0.23
3.22
1.23
1.23
0.35
6.96
1.62
1.62
0.46
11.04
1.99
1.99
0.57
15.7
2.35
2.35
0.68
21.19
17
0.8
0.8
0.23
3.24
1.23
1.23
0.35
6.98
1.62
1.62
0.47
11.07
1.99
1.99
0.57
15.76
2.36
2.36
0.68
21.27
19
1.13
0.76
0.33
6.03
1.37
1.2
0.39
8.29
1.64
1.62
0.47
11.25
1.99
1.99
0.57
15.81
2.36
2.36
0.68
21.35
20
-
-
-
-
1.87
1.18
0.54
14.13
1.89
1.52
0.56
15.18
2.12
1.99
0.6
17.31
2.36
2.35
0.68
21.31
4
15
0.52
0.52
0.11
0.86
1.07
1.07
0.23
3.24
1.5
1.5
0.33
6.01
1.89
1.89
0.41
8.86
2.26
2.26
0.49
12.02
17
0.52
0.52
0.11
0.86
1.07
1.07
0.23
3.26
1.51
1.51
0.33
6.03
1.89
1.89
0.41
8.89
2.26
2.26
0.49
12.06
19
0.53
0.51
0.11
0.88
1.11
1.06
0.24
3.5
1.5
1.5
0.33
6.04
1.9
1.9
0.41
8.92
2.27
2.27
0.49
12.11
20
-
-
-
-
1.4
1.02
0.3
5.36
1.68
1.47
0.36
7.18
1.95
1.89
0.42
9.28
2.27
2.26
0.49
12.1
5
15
0.38
0.38
0.07
0.49
0.73
0.73
0.13
0.99
1.34
1.34
0.23
3.29
1.77
1.77
0.31
5.4
2.16
2.16
0.37
7.54
17
0.38
0.38
0.07
0.49
0.74
0.74
0.13
1
1.34
1.34
0.23
3.31
1.77
1.77
0.31
5.42
2.16
2.16
0.37
7.57
19
0.38
0.37
0.07
0.49
0.74
0.74
0.13
1
1.34
1.34
0.23
3.33
1.77
1.77
0.31
5.44
2.16
2.16
0.37
7.6
20
-
-
-
-
0.74
0.72
0.13
1.01
1.4
1.33
0.24
3.64
1.78
1.77
0.31
5.49
2.17
2.17
0.37
7.61
6
15
-
-
-
-
0.6
0.6
0.09
0.64
0.96
0.96
0.14
1.11
1.6
1.6
0.23
3.23
2.03
2.03
0.29
4.99
17
-
-
-
-
0.6
0.6
0.09
0.64
0.96
0.96
0.14
1.11
1.6
1.6
0.23
3.25
2.03
2.03
0.29
5
19
-
-
-
-
0.6
0.6
0.09
0.65
0.96
0.96
0.14
1.12
1.6
1.6
0.23
3.27
2.04
2.04
0.29
5.02
20
-
-
-
-
0.6
0.6
0.09
0.65
0.96
0.96
0.14
1.12
1.6
1.6
0.23
3.26
2.04
2.04
0.29
5.03
Abbreviations:
EWT: Enter Water Temp. ()
Δt: Temperature Difference ()
DB: Dry Bulb Temp. ()
WF: Water Flow (m
3
/h)
WB: Wet Bulb Temp. ()
TC: Total Cooling Capacity (kW)
SC: Sensible Cooling Capacity (kW)
WPD: Water Pressure Drop (kPa)