Midea AC Fan Coil Unit
8
(Continued)
MKH2(3)-150-R3
EWT
ΔT
Indoor
tempe
(W.B.)
Indoor temperature (D.B.)
21
23
25
27
29
TC
SC
WF
WPD
TC
SC
WF
WPD
TC
SC
WF
WPD
TC
SC
WF
WPD
TC
SC
WF
WPD
°C
°C
°C
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
kW
kW
m^3/h
kPa
11
3
15
0.57
0.57
0.17
5.14
0.77
0.77
0.22
8.27
0.97
0.97
0.28
12.64
1.14
1.14
0.33
17.03
1.3
1.3
0.38
21.81
17
0.65
0.56
0.19
6.41
0.81
0.77
0.23
9.26
0.97
0.97
0.28
12.77
1.14
1.14
0.33
17.1
1.31
1.31
0.38
21.9
19
1.45
0.69
0.41
25.73
1.44
0.84
0.41
25.52
1.42
0.99
0.41
25.14
1.42
1.15
0.41
25.21
1.43
1.3
0.41
25.48
20
-
-
-
-
1.72
0.85
0.49
35.29
1.7
0.99
0.49
34.8
1.69
1.16
0.49
34.87
1.68
1.31
0.49
34.39
4
15
0.52
0.52
0.11
2.29
0.66
0.66
0.14
3.98
0.82
0.82
0.18
5.66
1.01
1.01
0.22
8.32
1.21
1.21
0.26
11.26
17
0.54
0.5
0.12
2.52
0.66
0.66
0.14
3.99
0.82
0.82
0.18
5.67
1.02
1.02
0.22
8.37
1.21
1.21
0.26
11.3
19
0.81
0.44
0.18
5.65
0.84
0.61
0.18
5.99
0.97
0.81
0.21
7.72
1.13
1.02
0.24
10.02
1.25
1.21
0.27
11.98
20
-
-
-
-
1.47
0.76
0.32
15.97
1.46
0.91
0.31
15.64
1.44
1.06
0.31
15.42
1.47
1.22
0.32
15.89
5
15
0.47
0.47
0.08
1.16
0.61
0.61
0.11
2
0.75
0.75
0.13
3.31
0.89
0.89
0.15
4.55
1.06
1.06
0.18
6.11
17
0.48
0.46
0.08
1.2
0.61
0.61
0.11
2
0.75
0.75
0.13
3.32
0.9
0.9
0.15
4.56
1.06
1.06
0.18
6.14
19
0.64
0.38
0.11
2.19
0.7
0.55
0.12
2.77
0.79
0.73
0.14
3.64
0.9
0.89
0.16
4.63
1.07
1.06
0.18
6.15
20
-
-
-
-
0.82
0.51
0.14
3.9
0.87
0.68
0.15
4.37
0.97
0.86
0.17
5.24
1.12
1.06
0.19
6.67
6
15
0.42
0.42
0.06
0.77
0.57
0.57
0.08
1.17
0.71
0.71
0.1
1.83
0.84
0.84
0.12
2.83
0.98
0.98
0.14
3.88
17
0.43
0.42
0.06
0.78
0.57
0.57
0.08
1.17
0.71
0.71
0.1
1.84
0.85
0.85
0.12
2.84
0.98
0.98
0.14
3.89
19
0.53
0.35
0.07
1.06
0.62
0.52
0.09
1.37
0.73
0.69
0.1
1.95
0.85
0.85
0.12
2.85
0.98
0.98
0.14
3.9
20
-
-
-
-
0.71
0.47
0.1
1.83
0.78
0.65
0.11
2.36
0.88
0.81
0.13
3.12
0.99
0.98
0.14
3.96
13
3
15
0.43
0.43
0.12
2.95
0.58
0.58
0.17
5.15
0.77
0.77
0.23
8.69
0.97
0.97
0.28
12.71
1.14
1.14
0.33
16.94
17
0.43
0.43
0.12
2.95
0.58
0.58
0.17
5.16
0.78
0.78
0.23
8.72
0.98
0.98
0.28
12.75
1.14
1.14
0.33
17.01
19
0.75
0.42
0.22
8.11
0.81
0.6
0.23
9.12
0.91
0.79
0.26
11.27
1.01
0.98
0.29
13.7
1.15
1.14
0.33
17.02
20
-
-
-
-
1.26
0.67
0.36
20.22
1.25
0.83
0.36
19.82
1.25
0.98
0.36
19.75
1.28
1.14
0.37
20.62
4
15
0.38
0.38
0.08
1.17
0.52
0.52
0.11
2.37
0.66
0.66
0.14
3.93
0.83
0.83
0.18
5.8
1.03
1.03
0.22
8.49
17
0.38
0.38
0.08
1.17
0.52
0.52
0.11
2.39
0.66
0.66
0.14
3.94
0.83
0.83
0.18
5.82
1.04
1.04
0.22
8.53
19
0.47
0.32
0.1
1.81
0.55
0.49
0.12
2.75
0.67
0.66
0.14
3.98
0.83
0.83
0.18
5.84
1.04
1.04
0.22
8.57
20
-
-
-
-
0.64
0.45
0.14
3.75
0.73
0.63
0.16
4.65
0.88
0.83
0.19
6.46
1.07
1.04
0.23
8.92
5
15
0.33
0.33
0.06
0.68
0.47
0.47
0.08
1.15
0.61
0.61
0.11
2.02
0.75
0.75
0.13
3.26
0.9
0.9
0.15
4.46
17
0.36
0.36
0.05
0.69
0.47
0.47
0.08
1.15
0.61
0.61
0.11
2.03
0.75
0.75
0.13
3.27
0.9
0.9
0.15
4.47
19
0.37
0.28
0.06
0.77
0.49
0.46
0.08
1.21
0.61
0.61
0.11
2.04
0.75
0.75
0.13
3.28
0.9
0.9
0.15
4.49
20
-
-
-
-
0.54
0.41
0.09
1.53
0.64
0.59
0.11
2.28
0.76
0.75
0.13
3.32
0.9
0.9
0.15
4.49
6
15
0.27
0.27
0.04
0.46
0.42
0.42
0.06
0.73
0.57
0.57
0.08
1.14
0.7
0.7
0.1
1.84
0.84
0.84
0.12
2.83
17
0.27
0.27
0.04
0.46
0.42
0.42
0.06
0.73
0.57
0.57
0.08
1.15
0.71
0.71
0.1
1.84
0.84
0.84
0.12
2.84
19
0.29
0.24
0.04
0.49
0.43
0.42
0.06
0.74
0.57
0.57
0.08
1.14
0.71
0.71
0.1
1.85
0.84
0.84
0.12
2.85
20
-
-
-
-
0.46
0.38
0.07
0.81
0.58
0.55
0.08
1.2
0.71
0.71
0.1
1.86
0.84
0.84
0.12
2.85
15
3
15
0.28
0.28
0.08
1.15
0.43
0.43
0.12
2.94
0.59
0.59
0.17
5.13
0.79
0.79
0.23
8.7
0.98
0.98
0.28
12.56
17
0.28
0.28
0.08
1.16
0.43
0.43
0.12
2.95
0.59
0.59
0.17
5.14
0.79
0.79
0.23
8.74
0.98
0.98
0.28
12.61
19
0.31
0.26
0.09
1.36
0.43
0.43
0.12
2.96
0.59
0.59
0.17
5.17
0.8
0.8
0.23
8.78
0.98
0.98
0.28
12.66
20
-
-
-
-
0.48
0.39
0.14
3.61
0.62
0.58
0.18
5.61
0.81
0.8
0.23
9
0.98
0.98
0.28
12.65
4
15
0.23
0.23
0.05
0.58
0.38
0.38
0.08
1.15
0.52
0.52
0.11
2.39
0.66
0.66
0.14
3.85
0.85
0.85
0.18
5.95
17
0.23
0.23
0.05
0.58
0.38
0.38
0.08
1.15
0.52
0.52
0.11
2.4
0.66
0.66
0.14
3.86
0.85
0.85
0.18
5.98
19
0.24
0.22
0.05
0.6
0.38
0.38
0.08
1.15
0.52
0.52
0.11
2.41
0.66
0.66
0.14
3.87
0.85
0.85
0.18
6
20
-
-
-
-
0.4
0.36
0.09
1.28
0.52
0.52
0.11
2.42
0.66
0.66
0.14
3.88
0.85
0.85
0.18
6.02
5
15
0.17
0.17
0.03
0.34
0.33
0.33
0.06
0.66
0.47
0.47
0.08
1.16
0.61
0.61
0.11
2.1
0.75
0.75
0.13
3.27
17
0.17
0.17
0.03
0.34
0.33
0.33
0.06
0.66
0.47
0.47
0.08
1.16
0.61
0.61
0.11
2.11
0.75
0.75
0.13
3.28
19
0.17
0.17
0.03
0.34
0.33
0.33
0.06
0.66
0.47
0.47
0.08
1.16
0.61
0.61
0.11
2.12
0.75
0.75
0.13
3.29
20
-
-
-
-
0.34
0.32
0.06
0.67
0.47
0.47
0.08
1.16
0.61
0.61
0.11
2.12
0.75
0.75
0.13
3.29
6
15
-
-
-
-
0.27
0.27
0.04
0.44
0.42
0.42
0.06
0.7
0.56
0.56
0.08
1.14
0.7
0.7
0.1
1.88
17
-
-
-
-
0.27
0.27
0.04
0.44
0.42
0.42
0.06
0.7
0.57
0.57
0.08
1.14
0.7
0.7
0.1
1.88
19
-
-
-
-
0.27
0.27
0.04
0.44
0.42
0.42
0.06
0.7
0.57
0.57
0.08
1.14
0.7
0.7
0.1
1.89
20
-
-
-
-
0.27
0.27
0.04
0.44
0.42
0.42
0.06
0.7
0.57
0.57
0.08
1.14
0.71
0.71
0.1
1.89
Abbreviations:
EWT: Enter Water Temp. ()
Δt: Temperature Difference ()
DB: Dry Bulb Temp. ()
WF: Water Flow (m
3
/h)
WB: Wet Bulb Temp. ()
TC: Total Cooling Capacity (kW)
SC: Sensible Cooling Capacity (kW)
WPD: Water Pressure Drop (kPa)