21
10  TEST RUNNING
Operate according to "key points for test running" on the electric control box cover. 
11  PRECAUTIONS ON REFRIGERANT LEAKAGE 
● Test  running  can  not  start  until  the  outdoor  unit  has  been connected to the power for 12 hours. 
●  Test running can not start until all the valves are affirmed open.
●  Never  make  the  forced  running  .(Or  the  protector  sits  back, danger will occur.)
CAUTION
Room is filled of leakage refrigerant
(All refrigerant has leaked out.)
4/6kW  Fig.11-1
Outdoor Unit
Indoor Unit
Install  mechanical  ventilator  to  reduce  the  refrigerant  thickness ,under critical level. (ventilate regularly).
Install leak alarm facility related to mechanical ventilator if you can not regularly ventilate. 
2
Requirments for charge limits in unventilated areas:
The maximum refrigerant charge in appliance shall be in accordance with the following:
                                                         m
max = 2.5 x (LFL)    x 1.8 x (A)
or the required minium floor area Amin to install an appliance with refrigerant charge m
c shall be in  accordance with following:
                                                        A
min=( mc / ( 2.5 x (LFL)    x 1.8))
where
m
max  is the allowable maximumm charge in a room,in kg
A  is the room area, in m
A
min  is the required minimum room area ,in m
m
c  is the refrigerant charge in appliance,in kg
LFL  is the lower flammable limit in kg/m  ,the value is 0.306 for R32 refrigerant
5/4                                   1/2
3
5/4                       2
●
●
●
When the refrigerant charge in appliance is more than 1.842kg, following requirments should be complied with.
2