●  When refrigerant pipe diameter is different from that of outdoor unit union (for 18K&24K indoor unit), 
additional transfer connector needs to be used on outdoor unit union. 
                                                                                                           
Indoor unit 
Extension pipe diameter (mm/inch) 
Model  Pipe diameter (mm/inch) 
7K9K12K 
Liquid  6.35(1/4)  Liquid  6.35(1/4) 
Gas  9.52(3/8)  Gas  9.52(3/8) 
18K 
Liquid  6.35(1/4)  Liquid  6.35(1/4) 
Gas  12.7(1/2)  Gas  12.7(1/2) 
24K  Liquid  9.52(3/8)  Liquid  9.52(3/8) 
Gas  15.9(5/8)  Gas  15.9(5/8) 
Outdoor unit union diameter (mm/inch) 
1 drive 2 
Liquid 
6.35(1/4)
 *2
 
Gas
 
9.52(3/8)
 *2
 
1 drive 3
 
Liquid 
6.35(1/4)
 *3
 
Gas
 
9.52(3/8)
 *3
 
1 drive 4
 
Liquid 
6.35(1/4)
 *4
 
Gas
 
9.52(3/8)
 *3
 
12.7(1/2)
 *
1
 
1 drive 5
 
Liquid 
6.35(1/4)
 *5
 
Gas
 
9.52(3/8)
 *4
 
12.7(1/2)
 *
1 
 
8.4 Installation for the first time 
Air and moisture in the refrigerant system have undesirable effects as below:   
●  Pressure in the system rises. 
●  Operating current rises. 
●  Cooling or heating efficiency drops. 
●  Moisture in the refrigerant circuit may freeze and block capillary tubing. 
●  Water may lead to corrosion of parts in the refrigerant system. 
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and 
evacuated to remove gas and moisture from the system. 
Gas leak check (Soap water method): 
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit connections 
by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out, the pipes 
have leakage. 
1. Air purging with vacuum pump