Aqua Tempo Super II Series DC Inverter Air-cooled chiller unit (50Hz) MCAC-ATSM-201704
55
4. The connected fixed wires must be equipped with full switching-off devices with at least 3mm contact
separation.
5. Set leakage protective devices according to the requirements of national technical standard about electric
equipment.
6. After completing all wiring construction, conduct careful check before connecting the power supply.
7. Please carefully read the labels on the electric cabinet.
8. The user’s attempt to repair the controller is prohibited, since improper repair may cause electric shock,
damages to the controller, and so on. If the user has any requirement of repair, please contact the
maintenance center.
15.3.2 Power supply specification
Model
Outdoor power supply
Wiring
Power supply Manual switch Fuse
MC-SU30-RN1L 380-415V 3Ph50Hz 50A 36A
16mm
2
(<20m)
MC-SU60-RN1L 380-415V 3Ph50Hz 100A 70A
25mm
2
(<20m)