Electrical Control Function
Electrical Control System 183
1.3.3 Heating Mode
1.3.2.1 Outdoor PMW open angle control
The unit is working in heating mode with the EXV open 300P for 3 minutes, then adjusting PMW open angle
according to the temperature of compressor discharge every 2 minutes.
1.3.3.2 Outdoor fan running rules:
For 12k models:
17
15
Low
High
For other models:
14
12
Low
High
1.3.3.3 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/(med)/low/auto. And the anti-cold wind
function has the priority.
Auto fan action:
For Compact cassette 12k
T1-TS-∆T
3
1
Low
High