Electrical Control Function
Electrical Control System 187
For 48K(1-Phase)、36-60K(3-Phase) models:
Condition of defrosting:
T4
3℃
Time1
Time2
Time conditions:
time1
Time conditions(Meet the following conditions)
1.Running in heating mode
2. T4≥3℃
3. Compressor is on
4. T3≤TempEnterDefrost_ADD ℃
Cleared conditions (Meet any one of the following conditions)
1. Compressor is off.
2. T3>TempEnterDefrost_ADD ℃
Time2
Time conditions (Meet the following conditions)
1.Running in heating mode
2. T4<3℃
3. Compressor is on
4. T3≤TempEnterDefrost_ADD ℃
Cleared conditions (Meet any one of the following conditions)
1. Compressor is off and T3
>TempEnterDefrost_ADD +2 last for 20 minutes℃
2. Running in cooling mode.
3. Compressor is off for 1 hour.
Condition of entry defrosting:
time1+ time2≥40 minutes, When defrosting is end,time1 and time2 are cleared.
Defrosting action: