Troubleshooting   
212  Electrical Control System 
 
2.4.2.8. E5 malfunction(For three phases units) 
Voltage protection 
Check the voltage of outdoor 
unit power supply, whether the 
voltage between L(1) 
,L(2),L(3)and N is about 
220VAC and between L(1) 
,L(2),L(3) is about 380VAC
Check the power supply
Check whether the voltage 
range of P-N on IPM module is 
normal? DC 350-650V
Replace bridge rectifiers, 
and then check whether the 
system can run normally 
Replace IPM board, and 
then check whether the 
system can run normally 
Replace outdoor main board
Yes
No
No
No
No
Yes
Trouble is solved
Yes
Yes
E5 display
Replace the power board, 
then check whether the 
system can run normally 
No
Yes