Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
2
Content
1 General information ................................................................................ 3
2. Features ................................................................................................... 5
3. Specification ........................................................................................... 9
4 Dimension .............................................................................................. 21
5 Refrigeration system drawing .............................................................. 33
6. Piping diagram ...................................................................................... 36
7 Wiring diagrams..................................................................................... 42
8 Electric characteristics ......................................................................... 56
9 Capacity tables ...................................................................................... 58
10 Exploded view ...................................................................................... 74
11 Troubleshooting ................................................................................... 96
12 Installation .......................................................................................... 108
13 Commissioning .................................................................................. 132
14 Maintenance ....................................................................................... 135
15 Control system .................................................................................. 137
Appendix ................................................................................................. 174

Questions and Answers

  • K
    ksingletonSep 8, 2025
    Why is the air side heat exchanger in my Midea MGB-D65W/RN1 excessively frosted?
    • M
      melissamoranSep 8, 2025
      Excessive frost on the air side heat exchanger can be due to a faulty 4-way valve or thermal resistor (check and replace if needed) or an air loop short-circuit (resolve the short-circuit).
  • J
    julia55Sep 10, 2025
    How to fix over low air discharge pressure in Midea Chiller (Heating operation)?
    • A
      Adam CollinsSep 10, 2025
      Low air discharge pressure during heating may be caused by low chilling water temperature (check it) or refrigerant leakage or insufficient refrigerant volume (test for leaks and recharge). If the air suction pressure is too low, see the section on “Excessive low air suction pressure”.
  • K
    Kayla PhillipsSep 12, 2025
    What to do if my Midea MGB-D65W/RN1 Chiller compressor can’t start?
    • T
      Timothy JonesSep 12, 2025
      If the compressor won't start, check for a tripped overcurrent relay or burnt fuse (replace), power to the control circuit (check wiring), high or low voltage protection (refer to air suction and discharge pressure error sections), burnt contactor coils (replace), incorrect phase sequence (reconnect any two of the three phases), water system error or shorted flow-type volume controller (check water system), or error signals from the wire controller (identify and address the error).
  • J
    James GonzalezSep 14, 2025
    What to do if my Midea MGB-D65W/RN1 compressor stops because of integrate temperature sensor or air discharge temperature protection?
    • A
      Amanda JohnsonSep 14, 2025
      If the compressor stops due to the integrated temperature sensor or air discharge temperature protection, check for high or low voltage (ensure it's within 20V of the rated voltage), high air expelling pressure or low air suction pressure (refer to those sections), or a component error (check the integrated temperature sensor after the motor cools down).
  • D
    David HuangSep 15, 2025
    What causes over low air suction pressure in Midea Chiller (Heating operation)?
    • L
      Lauren PattersonSep 15, 2025
      Low air suction pressure during heating can result from insufficient refrigerant (charge the system), insufficient air flow (check fan direction), an air loop short-circuit (remove the short-circuit), or insufficient frost-removal (replace the 4-way valve or thermal resistor if necessary).
  • K
    Kristina PhelpsSep 18, 2025
    What could cause abnormal noise from the compressor in my Midea MGB-D65W/RN1 Chiller?
    • E
      Erin WoodsSep 18, 2025
      Abnormal compressor noise can be due to liquid refrigerant entering the compressor from the evaporator, causing liquid slugging (adjust refrigerant charge), or the compressor aging (replace the compressor).

Summary

Key Features of Chiller Units

Low Ambient Temperature Cooling

Details the cooling and heating operating temperature ranges for specific models.

Wide Outlet Water Temperature Range

Describes selectable outlet water temperatures for cooling and heating modes.

Advanced Operational Features

Covers humanized remote control, digital scroll tech, modular design, and system combinations.

Technical Specifications

Refrigeration System Diagrams

Electrical Wiring Diagrams

7.1 Chiller Wiring Diagram

Illustrates the electrical connections for the main chiller unit.

Electric Characteristics Data

Performance Capacity Tables

Troubleshooting Guide

11.1 Failure & Protection Codes (25;30 kw Module)

Lists fault and protection codes for 25/30kw modules and their meanings.

11.2 Module-Specific Troubleshooting Codes

Provides fault and protection codes for new 30kw, 55/60/65kw, 130kw, 185kw, and 250kw modules.

11.3 Troubles and Solutions

Offers potential causes and solutions for common operational issues.

Installation Procedures

12.1 Unit Installation and Transportation

Covers physical setup, handling, and transport of the unit.

12.2 Installation Space Requirements

Specifies minimum clearance and site considerations for proper unit installation.

12.3 Installation Foundation

Details requirements for the installation base and foundation structure.

12.4 Water System Installation

Guides on connecting chilled water pipelines, including flushing and component requirements.

12.5 Wiring Installation

Provides instructions and precautions for electrical wiring connections.

Commissioning Procedures

13.1 Preparation Steps

Outlines necessary steps before starting up the unit, like flushing and pre-heating.

13.2 Test Run Procedure

Details the process for conducting a trial run and final checks.

Maintenance Guidelines

14.1 General Component Maintenance

Covers regular checks on pressure, connections, and electrical elements.

14.4 System Anti-Freezing Measures

Details measures to prevent freezing in the water-side heat exchanger and piping.

Control System Overview

15.1 PCB Outline and Component Description

Identifies key components and their functions on the main control boards.

15.2 Wired Controller Operation

Explains how to use the wired controller for system operation, settings, and querying.