The site contains mineral oils such as cutting lubricant.
Seaside where the air contains much salt.
Hotpring area where corrosive gases exist, e.g., sulfide gas.
Factories where the supply voltage fluctuates seriously.
Inside a car or cabin.
Place like kitchen where oil permeates.
Place where strong electromagnetic waves exist.
Place where flammable ga ses or materials exist.
Place where acid or alkali gases evaporate.
Other special environments.
Install the unit where enough space of installation and
maintenance is available.
Install the unit where the air inlet and air outlet are free from
obstacles and strong wind.
Install the unit in a dry and well ventilated place.
Install the unit where the bearing surface is level and can bear
weight of the unit, and is suitable for installing the unit
horizontally without increasing noise or vibration.
Install the unit where the operation noise and the expelling of air
do not affect neighbours.
Install the unit where no flammable gas is leaked.
Install the unit where it is convenient for pipe connection and
electric connection.
2
2. ACCESSORIES
NOTE
If in the wire control mode, the accessories do not include
display panel assembly remote controller or mounting bracket.
1
1
1
2
2
1
Accessory name of
indoor unit
Qty. Purpose
Owner’s manual
Shape
Installation manual
Sealing tape
Protective sleeve for
refrigerant inlet and
outlet pipes
Wired remote controller
Water connective pipe
This manual
Sealed tube interface
Connect to water drainage
pipe
Table 2-1
1
Copper nut
Connect to liquid-side pipe
Table 2-2
1
1
1
2
1
1
Accessory name of
outdoor unit
Qty. Purpose
Water outlet connection
pipe
Shape
Straight screwdriver
Sealing ring
Connection pipe
Waterproof chassis cover
Centralized drainage
Inspection and DIP
Centralized drainage
Chassis auxiliary drainage
plug
Curved connection pipe
Connecting pipe of system
13) Flare tool
14) Pipe bender
15) Level vial
16) Metal saw
17) Gauge manifold (Charge hose:R410A special requirement)
18) Vacuum pump (Charge hose:R410A special requirement)
19) Torque wrench
1/4(17mm)16N•m (1.6kgf•m)
3/8(22mm)42N•m (4.2kgf•m)
1/2(26mm)55N•m (5.5kgf•m)
5/8(15.9mm)120N•m (12.0kgf•m)
20) Copper pipe gauge adjusting projection margin
21) Vacuum pump adapter
Required tools for installation work
1) Philips screw driver
2) Hole core drill(65mm)
3) Spanner
4) Pipe cutter
5) Knife
6) Reamer
7) Gas leak detector
8) Tape measure
9) Thermometer
10) Mega-tester
11) Electro circuit tester
12) Hexagonal wrench
Refrigerant Piping
Piping kit used for the conventional refrigerant cannot be used.
Use copper pipe with 0.8 mm or more thickness for φ9.5mm.
Use copper pipe with 1.0 mm or more thickness for φ15.9mm.
Use copper pipe with 1.0 mm or more thickness for φ19.0mm.
Use copper pipe with 1.0 mm or more thickness for φ22.0mm.
Use copper pipe with 1.0 mm or more thickness for φ25.0mm.
Use copper pipe with 1.0 mm or more thickness for φ28.0mm.
Flare nut and flare works are also different form those of the
conventional refrigerant.take out the flare nut attached to the
main unit of the air conditioner, and use it.
Before installation
Be careful to the following items before installation.
Air purge
For air purge, use a vacuum pump.
Do not use refrigerant charged in the outdoor unit for air purge.
(The refrigerant for air purge is not contained in the outdoor unit.)
Electrical cabling
Be sure to fix the power cables and indoor/outdoor connecting
cables with clamps so that they do not contact with the cabinet,
etc.
Installation Place
A place which provides a specified space around the outdoor unit.
A place were the operation noise and discharged air are not
given to your neighbors.
A place that is not exposed to a strong wind.
A place that does not block a passage.
When the outdoor unit is installed in an elevated position, make
sure it's four feet securely installed.
There must be sufficient space for carrying in the unit.
A place where the drain water does not make any problem.