1.6 Heating Mode
1.6.1 Compressor Control
1) Reach the configured temperature
If the following conditions are satisfied, the
compressor ceases operation.
While calculated frequency(fb) is less than
minimum limit frequency(FminC).
When protective time is more than or equal to ten
minutes.
When T1 is higher than or equal to Tsc+
HDIFTEMP2.
Note: HDIFTEMP2 is EEPROM setting parameter. It is 2°C
usually.
If one of the following conditions is satisfied, not
judge protective time.
Compressor running frequency is more than test
frequency.
When compressor running frequency is equal to
test frequency, T4 is more than 15°C or no T4 or T4
fault.
Change setting temperature.
Turbo or sleep function on/off.
2) When the current is higher than the predefined safe
value, surge protection is activated, causing the
compressor to cease operations.
1.6.2 Indoor Fan Control:
1) In heating mode, the indoor fan operates continuously.
The fan speed can be set to 1%-100%, or mute.
2) Auto fan
Rise curve
When T1-Tsc is higher than -1.5°C, fan speed
reduces to 80%;
-When T1-Tsc is higher than 0°C, fan speed reduces
to 60%;
-When T1-Tsc is higher than 0.5°C, fan speed
reduces to 40%;
-When T1-Tsc is higher than 1°C, fan speed reduces
to 20%.
Descent curve
When T1-Tsc is lower than or equal to 0.5°C, fan
speed increases to 20%;
-When T1-Tsc is lower than or equal to 0°C, fan
speed increases to 60%;
-When T1-Tsc is lower than or equal to -1.5°C, fan
speed increases to 80%;
-When T1-Tsc is lower than or equal to -3°C, fan
speed increases to 100%.
1.6.3 Outdoor Fan Control:
The outdoor unit will be run at different fan speed
according to T4 and compressor running frequency.
For different outdoor units, the fan speeds are
different.
1.6.4 Defrosting mode
The unit enters defrosting mode according to changes
in the temperature value of T3, T4 as well as the
compressor running time.
In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the “ ” symbol is displayed.
If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
T3 rises above TCDE1°C.
T3 maintained above TCDE2°C for 80 seconds.
Unit runs for 15 minutes consecutively in defrosting
mode.
1.6.5 Evaporator Temperature Protection
When the evaporator temperature exceeds a preset
protection value, the compressor stops.
1.7 Auto-mode
This mode can be selected with the remote controller
and the setting temperature can be changed between
16°C~30°C.
In auto mode, the machine selects cooling, heating,
auto-drying or fan-only mode on the basis of T1,Ts, T4
and relative humidity.
If the setting temperature is modified, the machine
selects a new running function.
1.8 Drying mode
In drying mode, AC operates the same as auto fan in
cooling mode.
1) Mute function is active.
All protections are activated and operate the same as
they do that in cooling mode.
2) Low Room Temperature Protection
If the room temperature is lower than 10°C, the
compressor ceases operations and does not resume

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MISSION2 3D INVERTER Series and is the answer not in the manual?

Midea MISSION2 3D INVERTER Series Specifications

General IconGeneral
BrandMidea
ModelMISSION2 3D INVERTER Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals