Resume: No limitation for frequency. 
Note: 
When AC is in “hold” zone for 3 minutes, the 
compressor frequency will rise to the higher 
level. (The frequency will increase twice at 
most) 
8.4.3.2 Outdoor fan running rules 
 
 
8.4.3.3 Indoor fan running rules   
Indoor fan speed can be set as high, medium, 
low, silent mode or auto grade. During all the 
fan speeds, the anti-cold-wind function is 
preferential. If the compressor stops caused by 
the room temperature rising, the indoor fan will 
run at super breeze. When the compressor is 
running, the indoor fan is controlled as below: 
 
The anti-cold wind function is as below: 
For MS11M-09HRFN1-MW0W, 
MS11M-12HRFN1-MV0W, 
MS11M-18HRFN1-MU0W models: