Remark: 
Use a multimeter to test the DC voltage 
between L2 port and S port of outdoor 
unit. The red pin of multimeter connects 
with L2 port while the black pin is for S 
port.   
 
When AC is normal running, the voltage 
will move alternately between -50V to 
50V. 
 
If the outdoor unit has malfunction, the 
voltage will move alternately with positive 
value.   
 
While if the indoor unit has malfunction, 
the voltage will be a certain value. 
Remark: 
Use a multimeter to test the resistance 
of the reactor which does not connect 
with capacitor. 
The normal value should be around zero 
ohm. Otherwise, the reactor must have 
malfunction and need to be replaced.