Check if the power supply is 
normal.
Check if all the connections 
and wires are good?
Disconnect the unit with power 
supply and try to restart the unit 
when power supply gets normal.
No
Yes
No
Correct the connections or replace 
the wires.
Yes
Power on and when the unit is in 
standby, check if the voltage 
between P and N is around DC 
310V or 340V or 380V? For different 
kinds of units, the voltage differs. 
Consult with technical engineer to 
get definite value. Then start up the 
unit, measure the voltage between P 
and N. Is it in 220V~400V?
Replace outdoor main PCB.
Yes
No
Replace the IPM board if it is 
separate with main PCB.