61
2.Compressor checking
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
DA110S1C-30FZ
DA130M1C-31FZ
DA250S2C-30MT
Blue - Red
0.8Ω
(20°C /68°F)
1.77Ω
(20°C /68°F)
0.5
(20°C /68°F)
Blue - Black
Red - Blue

Related product manuals