minutes after starting and then judge temperature. Meanwhile other protections are still
valid.
Condition Compressor Outdoor fan
T> Ts+3 Off Off Room temp. up
T<Ts+3 On On
T< Ts+2 On On Room temp. down
T>Ts+2 Off Off
8.8.4 Indoor Fan actions at heating mode
8.8.4.1 Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but
Anti-cold wind function prevails.
8.8.4.2 Anti-cold wind control function at heating mode
Condition
T= Indoor exchanger temp.
Indoor fan speed
T<TE1 Off
TE1<T<TE2 Breeze
Indoor exchanger temp. up
T>TE2 Setting fan speed
T> TE3 Setting fan speed
TE3<T<TE4 Breeze
Indoor exchanger temp. down
T<TE4 Off
8.8.4.3 Auto wind
Condition
T=Indoor Temp.-Setting Temp.
Indoor fan speed
T<2℃ High Room temp. up
T>2℃ Med.
T> 0℃ Med. Room temp. down
T<0℃ High
8.8.4.4.Indoor evaporator high-temperature protection
Condition
T= Indoor exchanger temp.
Compressor Outdoor fan
T<TE8 On On
TE8<T<TE7 On Off
Indoor exchanger temp. up
T>TE7 Off Off
T>TE9 Off Off Indoor exchanger temp. down
T<TE9 On On
8.9 Defrosting operation (Available for heating only).
8.9.1 Defrosting condition: Defrosting starts when either of the following ①&②:
① A and B are satisfied:
153