8.11 Heating mode
8.8.6 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting
mode.
8.8.7 Generally, the outdoor fan is turned off with the on-off action of compressor in heating
mode, except for the defrosting mode or the end of defrost.
8.8.8 Action of compressor and outdoor fan motor at heating mode:
Condition Compressor Outdoor fan
T> Ts+3 Off Off Room temp. up
T<Ts+3 On On
T< Ts+2 On On Room temp. down
T>Ts+2 Off Off
8.8.9 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but
Anti-cold wind function prevails.
Anti-cold wind control function at heating mode
Condition
T= Indoor exchanger temp.
Indoor fan speed
T<TE1 Off
TE1<T<TE2 Breeze
Indoor exchanger temp. up
T>TE2 Setting fan speed
T> TE3 Setting fan speed
TE3<T<TE4 Breeze
Indoor exchanger temp. down
T<TE4 Off
8.8.10 Auto wind at heating mode
Condition
T=Indoor Temp.-Setting Temp.
Indoor fan speed
T<2 High Room temp. up
T>2 Med.
T> 0 Med. Room temp. down
T<0 High
8.8.7 Indoor evaporator high-temperature protection at heating mode
Condition
T= Indoor exchanger temp.
Compressor Outdoor fan
T<TE8 On On
TE8<T<TE7 On Off
Indoor exchanger temp. up
T>TE7 Off Off
T>TE9 Off Off Indoor exchanger temp. down
T<TE9 On On