13
 
6.4 Installation for the first time 
Air and moisture in the refrigerant system have 
undesirable effects as below: 
● Pressure in the system rises. 
●  Operating current rises. 
●  Cooling or heating efficiency drops. 
●  Moisture in the refrigerant circuit may 
freeze and block capillary tubing. 
●  Water when mixed with the refrigerant and oil 
will create an acid that will damage the motor 
windings and components in the refrigerant 
system. 
Therefore, the indoor units and the pipes 
between indoor and outdoor units must be leak 
tested and evacuated to remove gas and 
moisture from the system. 
Gas leak check (Soap water method): 
Apply soap water or a liquid neutral 
detergent on the indoor unit connections or 
outdoor unit Connections with a soft brush to 
check for leakage of the connecting points of 
the piping. If bubbles come out, the pipes have 
leakage. 
1. Air purging with vacuum pump 
 
1) Completely tighten the flare nuts of the 
indoor and outdoor units, confirm that both 
the 2-way and 3-way valves are set to the 
Front seated. 
2)  Connect the low pressure gauge to the 3 way 
service valve access port.. 
3)  Connect the middle hose of the gauge 
manifold (usually yellow) to the vacuum 
pump. 
4) Fully open the handle for the low pressure 
gauge.. 
5)  Start the vacuum pump and operate according 
to manufacture spec's. 
6)  Perform an evacuation for a minimum of 30 
minutes and check that the low pressure 
(compound) gauge indicates a vacuum of 29.9 
in/hg (500 microns) A vacuum gauge should 
be used if available. If the proper vacuum 
cannot be achieved the vacuum pump should 
be run for an additional 20 minutes. If after the 
additional 20 minutes the vacuum still cannot 
be achieved the is a leak in the system and 
must be located and repaired. follow the leak 
checking procedure as mentioned before. If 
the vacuum is achieved, close the low pressure 
gauge handle off and shut the vacuum pump 
off. Recheck the reading after 10 minutes, the 
vacuum may change slightly, this is normal. 
7)  The system is now dry and free of 
contaminates, refrigerant pressure should 
now be added to the system from a source 
other than the system before opening the 2 
way and 3 way valves for system operation. 
8)  The 2 way and 3 way valve can now be 
opened for the system operation 
 
2. Air purging by refrigerant 
 
Procedure: 
1). Confirm that both the 2-way and 3-way 
valves are set to the closed position. 
2). With a container of refrigerant and a gauge 
manifold set, connect the low pressure gauge hose