14
to the 3 way valve service port and a charging 
cylinder to the service port of the 3-way valve. 
3). Open the valve on the refrigerant container and 
the low pressure gauge to allow the refrigerant to 
enter the system, next loosen the flare connection 
on the 2 way valve line to purge the air and 
contaminants from the system for 30 to 50 
seconds, then retighten the connection. 
4). Next allow the pressure from the refrigerant to 
reach 100 psi and then close the low pressure 
gauge and the refrigerant container and check the 
2 way and 3 way valve line connections for leaks 
with liquid soap or electronic leak detector. 
5). After the system has been check for leaks the 
pressure should be adjusted to about 25 to 50 psi. 
6). You can now disconnect the gauge manifold 
and refrigerant container from the system and 
open the 2 way and 3 way valves for system 
operation 
7). Mount the valve stems nuts and the service 
port cap. 
Be sure to use a torque wrench to tighten the 
service port cap to a torque 18N·m(13.27 ft.lbs). 
Be sure to check the gas leakage. 
6.5 Adding the refrigerant after running 
the system for many years 
 
Procedure 
1). 1st step; Connect the low pressure gauge from 
the gauge manifold set to the 3 way service valve 
(this is the blue hose on most sets) 2nd step; 
Connect the middle hose from the manifold set to 
the refrigerant container (this is the yellow line on 
most sets). with refrigerant 410A the container 
must be inverted (upside down) when adding the 
refrigerant. Note that the 2 way and 3 way valves 
must be in the open position. 
3rd step; the air in the gauge hoses needs to be 
purged out. use the pressure from the system to 
purge the low side line, loosen the connection on 
the manifold for a second, next open the to valve 
on the refrigerant container to pressurize the line, 
now loosen that hose at the manifold for a second 
and purge that line. 
3) Next step is to set the refrigerant container on 
an electronic charging scale and record the weight 
or zero the scale depending on the scale used. 
Next determine the refrigerant charge to be 
added. 
4) Start the unit in the cooling mode and lower the 
set point so the unit wont shut off during the 
charging procedure. 
5) Refrigerant can now be added to the system, 
open the low pressure valve on the gauge manifold 
set to start charging the unit with liquid refrigerant, 
keep track of the refrigerant being added to the 
system (do not overcharge the system) 
6). Once the correct charge has been added to the 
system close the low pressure valve on the gauge 
manifold set and record the operating pressure. 
The system is now charged and the unit can be 
shut off. Close the valve on the refrigerant 
container and disconnect the hose from the 
manifold set, also disconnect the hose from the 3 
way valve and replace and torque all caps. 
7). Mount the valve stem caps and the service 
port 
Use torque wrench to tighten the service port 
cap to a torque of 18N.m(13.27 ft,lbs). 
Always leak check after servicing the refrigerant 
system. 
6.6 Procedure when servicing the indoor 
unit refrigeration circuit. 
1. Pumping down the system (isolating the 
refrigerant charge in the condensing unit)