22
8.4.4 Auto-mode 
This mode can be chosen with remote 
controller and the setting temperature can be 
changed between 17°C(62.6°F)~30°C(86°F). 
In auto mode, the machine will choose cooling, 
heating or fan-only mode according to ΔT  
(ΔT =T1-Ts). 
T1-Ts
Cooling
Heating*
Fan only
 
Heating*: For cooling only models, they will run 
at fan speed 
Indoor fan will run at auto fan of the relevant 
mode. 
The louver operates same as in relevant mode. 
If the machine switches mode between heating 
and cooling, the compressor will keep stopping 
for certain time and then choose mode 
according to T1-Ts. 
If the setting temperature is modified, the 
machine will choose running function again. 
 
8.4.5 Drying mode 
8.4.5.1 Indoor fan speed is fixed at breeze and 
can’t be changed. The louver angle is the same 
as in cooling mode. 
8.4.5.3 Low indoor room temperature protection 
In drying mode, if room temperature is lower 
than 10°C(50°F), the compressor will stop and 
not resume until room temperature exceeds 
12°C(53.6°F). 
8.4.5.4 Evaporator anti-freezing protection, 
condenser high temperature protection and 
outdoor unit frequency limit are active and the 
same as that in cooling mode. 
8.4.5.5 The outdoor fan operates the same as 
in cooling mode. 
 
8.4.6 Forced operation function 
8.4.6.1 Enter forced operation function: 
When the machine is off, pressing the touch 
button will carry the machine to forced auto 
mode. If pressing the button once again within 
5 seconds, the machine will turn into forced 
cooling mode. 
In forced auto, forced cooling or any other 
operation mode, pressing touch button will turn 
off the machine. 
8.4.6.2 In forced operation mode, all general 
protections and remote control are available. 
8.4.6.3 Operation rules: 
Forced cooling mode: 
The compressor runs at F2 frequency and 
indoor fan runs as breeze. After running for 30 
minutes. the machine will turn to auto mode as 
24°C(75.2°F) setting temperature. 
Forced auto mode: 
The action of forced auto mode is the same as 
normal auto mode with 24°C(75.2°F) setting 
temperature. 
 
8.4.7 Auto-Restart function 
The indoor unit is equipped with auto-restart 
function, which is carried out through an 
auto-restart module. In case of a sudden power 
failure, the module memorizes the setting 
conditions before the power failure. The unit will 
resume the previous operation setting (not 
including swing function) automatically after 3 
minutes when power returns. 
If the memorization condition is forced cooling 
mode, the unit will run in cooling mode for 30 
minutes and turn to auto mode as 24°C(75.2°F) 
setting temp. 
If AC is off before power off and AC is required 
to start up now, the compressor will have 1 
minute delay when power on. Other conditions, 
the compressor will have 3 minutes delay when 
restarts.