17.4.13. J0 Malfunction 
When evaporator coil temperature is more than 60°C, the unit stops. It starts again 
only when the evaporator coil temperature is less than 54°C 
J0 displayed
J0 displayed
Evaporator high temperature protection 
Evaporator high temperature protection 
Is the compressor operating?
Is the compressor operating?
Yes
Is the outdoor ambient 
temperature is higher than 30℃?
Is the outdoor ambient 
temperature is higher than 30℃?
No
Correct the connection
Correct the connection
No
Is the connection 
between T2 and The 
PCB is in working order?
Have T2 and T2B  been 
reversed?
Is the connection 
between T2 and The 
PCB is in working order?
Have T2 and T2B  been 
reversed?
Is the resistance of T2 
normal according to 
Appendix 1?
Is the resistance of T2 
normal according to 
Appendix 1?
Replace the temperature sensor
Replace the temperature sensor
No
Yes
Yes
Stop the unit 
Stop the unit 
Yes
Is the air-outlet blocked?
Is the air-outlet blocked?
Are the heat exchanger and 
filter dirty?
Are the heat exchanger and 
filter dirty?
Is the indoor fan running 
normally?
Is the indoor fan running 
normally?
No
Yes
Clean  the air-outlet
Clean  the air-outlet
Replace the indoor main 
PCB
Replace the indoor main  
PCB
Clean the heat exchanger and filter
Clean the heat exchanger and filter
Yes
No
Yes
Refer to the solution for the 
malfunction of the fan speed being out 
of control . Find the cause and resolve 
the problem
Refer to the solution for the 
malfunction of the fan speed being out 
of control . Find the cause and resolve 
the problem
No
No