L8 protection
ODU stop valves are closed Open the ODU stop valves
Reconnect the cables based on 
wiring diagram
The resistance between 3 phases of 
compressor is over 5Ω 
Replace the compressor
The insulation resistance of 
compressor is less than 100Ω 
Replace the compressor inverter 
board, restart the unit and the error is 
solved
Refer to P1 or P3 troubleshooting
No
Yes
Disconnect the 
power supply
Compressor wiring is not properly
Yes
Normal
Yes
Yes
Yes
No
No
No
No
L9 protection
The compressor has less than 12 hours 
preheating before initial operating
Ensure enough preheating time
Yes