V6-i VRF 50/60Hz       
72     
Midea V6-i Series Service Manual
 
2.2 E1: Phase sequence error 
 Digital display output 2.2.1
   
 
 Description 2.2.2
  Phase sequence error. 
  All units stop running. 
  Error code is displayed on the outdoor unit with the error. 
 
 Trigger / recover condition 2.2.3
  Trigger condition: Wrong phase connection for 1.6s or phase missing for 48s. 
  Recover condition: Correct phase connection. 
  Reset method: Manually restart. 
   
 Possible causes 2.2.4
  Power supply phases not connected in correct sequence. 
  Power supply terminals loose. 
  Power supply abnormal. 
  Main PCB damaged.