Midea V6-i Series Service Manual
 
3.2 Normal Operating Parameters of Refrigerant System 
Under the following conditions, the operating parameters given in Tables 5-5.4 and 5-5.5 should be observed: 
  The outdoor unit can detect all the indoor units. 
  The number of indoor units displayed on DSP2 is steady and is equal to the actual number of indoor units installed. 
  All stop valves are open and all indoor unit EXVs are connected to their unit’s PCB. 
  If the combination ratio is 100% or less, all the indoor units are currently running and if the combination ratio is more 
than 100%, indoor units with total capacity equal to the capacity of the outdoor unit are currently running. 
  If  the  outdoor  ambient  temperature  is  high,  the  system  is  being  run  in  cooling  mode  with  the  following  settings: 
temperature 17°C ; fan speed high. 
  If  the  outdoor  ambient  temperature  is  low,  the  system  is  being  run  in  heating  mode  with  the  following  settings: 
temperature 30°C ; fan speed high. 
  The system has been running normally for more than 30 minutes. 
 
Table 6-3.4: Outdoor unit cooling mode operating parameters 
Outdoor ambient temperature   
Average discharge temperature 
Average discharge superheat 
DC inverter compressor current 
 
Table 6-3.5: Outdoor unit heating mode operating parameters 
Outdoor ambient temperature   
Average discharge temperature 
Average discharge superheat 
DC inverter compressor current