V6-i VRF 50/60Hz 
    119 
Part 
6 - Diagnosis and Troubleshooting
 
2.21 P9, H9: Fan module protection 
 Digital display output 2.21.1
  ;       
 
 Description 2.21.2
  Fan module protection.   
  All units stop running. 
  Error code is only displayed on the unit with the error. 
 
 Trigger / recover condition 2.21.3
  Trigger condition:   
For P9 protection: Fan speed is too low. 
For H9 protection: P9 protection appears ten times in 120 minutes. 
  Recover condition: Fan speed go back to normal. 
  Reset method:   
For P9 protection: Resume automatically; For H9 protection: Manually restart. 
 
 Possible causes 2.21.4
  Switch ENC2 incorrectly set. 
  Power or communication wires not connected properly. 
  Fan motor blocked or has failed. 
  Power supply abnormal. 
  AC filter board damaged. 
  Fan module damaged. 
  Main PCB damaged. 
 
 Procedure 2.21.5
 
The capacity set on switch ENC2 on the 
main PCB and the capacity given on the 
unit’s nameplate do not match 
Ensure the setting on switch ENC2 
matches the unit capacity given on the 
unit’s nameplate 
Some power wires or communication 
wires of fan module are not connected 
properly 
Ensure power and communication wires 
are connected properly 
The fan motor is blocked or has failed 
Remove obstruction or replace the fan 
motor 
Flowchart  continued  on  next  page  …