V6-i VRF 50/60Hz 
    121 
Part 
6 - Diagnosis and Troubleshooting
 
2.22 PL, C7: Inverter module temperature protection 
 Digital display output 2.22.1
     
   
'x'  is  a  placeholder  for  the  compressor  system  (compressor  and  related  electrical  components),  with  1  representing 
compressor system A and 2 representing compressor system B. 
 
 Description 2.22.2
  1PL indicates inverter module A temperature protection.   
  2PL indicates inverter module B temperature protection.   
  All units stop running. 
  Error code is only displayed on the unit with the error. 
 
 Trigger / recover condition 2.22.3
  Trigger condition:   
For PL protection: Inverter module heat sink temperature (TF1/2) ≥ 80
o
C. 
For C7 protection: PL protection appears three times in 100 minutes. 
  Recover condition: Inverter module heat sink temperature (TF1/2) < 65
o
C 
  Reset method:   
For PL protection: Resume automatically. 
For C7 protection: Manually restart. 
 
 Possible causes 2.22.4
  Blocked, dirty or loose heat sink. 
  Temperature sensor not connected properly or has malfunctioned. 
  Main PCB damaged.