V6-i VRF 50/60Hz 
    115 
Part 
6 - Diagnosis and Troubleshooting
 
2.19 P4, H6: Discharge temperature protection 
 Digital display output 2.19.1
  ;       
 
 Description 2.19.2
  Discharge temperature protection.   
  All units stop running. 
  Error code is only displayed on the unit with the error. 
 
 Trigger / recover condition 2.19.3
  Trigger condition:   
For P4 protection: Discharge temperature (T7C1/2) ≥ 120
o
C. 
For H6 protection: P4 protection appears three times in 100 minutes. 
  Recover condition: Discharge temperature (T7C1/2) ≤ 90
 o
C. 
  Reset method:   
For P4 protection: Resume automatically. 
For H6 protection: Manually restart. 
 
 Possible causes 2.19.4
  Outdoor unit stop valves are closed. 
  Temperature  sensor/switch  not  connected 
properly or has malfunctioned. 
  Insufficient refrigerant. 
  System blockage. 
  Indoor load too large. 
  System contains air or nitrogen. 
  Poor condenser heat exchange. 
  Main PCB damaged. 
 
 Procedure 2.19.5
 
ODU stop valves are closed 
Compressor top temperature sensor, 
discharge pipe temperature sensor 
and/or discharge temperature switch 
connections on main PCB are loose
1
 
Ensure the sensors and switch are 
connected properly 
Compressor top temperature sensor 
and/or discharge pipe temperature 
sensor have short circuited or failed
2
 
Replace the faulty sensor(s) 
Flowchart  continued  on  next  page  … 
… flowchart continued from previous page