V6-i VRF 50/60Hz       
124     
Midea V6-i Series Service Manual
 
 Procedure 2.23.5
 
Compressor top temperature sensor 
and/or discharge pipe temperature 
sensor connections on main PCB are 
loose
1
 
Ensure the sensors are connected 
properly 
Compressor top temperature sensor 
and/or discharge pipe temperature 
sensor have short circuited or failed
2
 
Replace the faulty sensor(s) 
Poor heat insulation of compressor top 
temperature sensor resulting in 
temperature reading lower than actual 
temperature 
Ensure sufficient heat insulation for 
compressor top temperature senor 
Discharge part of the refrigerant. Add oil 
if it leaks during discharge 
Discharge pressure is too high 
Troubleshoot as for a P1 error
4
 
 
Notes:   
1.  Compressor  top  temperature  sensor  and  discharge  pipe  temperature  sensor  connections  are  ports  CN4  and  CN5  on  the  main  PCB  (labeled  3  and  4, 
respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).   
2.  Measure  sensor  resistance.  If  the  resistance  is  too  low,  the  sensor  has  short-circuited.  If  the  resistance  is  not  consistent  with  the  sensor’s  resistance 
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”. 
3.  Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher 
than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 
4.  See “P1 Troubleshooting”.