Midea V6-i Series Service Manual
 
Tables 3-7.3 and 3-7.4 show component control during oil return operation in heating mode.   
Table 3-7.3: Outdoor unit component control during oil return operation in heating mode 
Control functions and states 
Fan  speed  controlled  according 
to discharge pressure   
Electronic expansion valve A 
Position  480  (steps)  or  3000 
(steps) 
Electronic expansion valve C 
Solenoid valve (oil balance) 
Solenoid valve (fast defrosting) 
Solenoid valve (EXV bypass) 
Solenoid  valve  (indoor  units 
bypass) 
Solenoid  valve  (inverter 
compressor A vapor injection) 
Solenoid  valve  (inverter 
compressor B vapor injection) 
Solenoid  valve  (inverter 
compressor B pressure balance) 
Open  before  compressor  B 
startup 
 
Table 3-7.4: Indoor unit component control during oil return operation in heating mode 
Control functions and states 
Electronic expansion valve