V6-i VRF 50/60Hz 
    79 
Part 
6 - Diagnosis and Troubleshooting
 
 Procedure 2.5.5
 
ODU power supply is abnormal or a 
phase is missing
1
 
Provide normal power supply 
Wires between outdoor main PCB, AC 
filter boards and electric control box 
power supply terminals are loose   
Ensure the wires are connected properly 
High voltage circuit error has occurred, 
such as the compressor has 
malfunctioned
2
, the fan motor has 
short-circuited
3
, or the inverter module 
has short-circuited
4
 
Replace or repair the relevant parts 
 
Notes:   
1.  The normal voltage between A and N, B and N, and C and N is 198-242V. 
2.  The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances 
differ from these specifications, the compressor has malfunctioned. 
3.  The normal resistances of the fan motor coil among U V W are less than 10Ω. If a measured resistance is 0Ω, the fan motor has short-circuited.   
4.  Set  a  multi-meter  to  buzzer  mode  and  test  any  two  terminals  of  P  N  U  V  W  of  the  inverter  module.  If  the  buzzer  sounds,  the  inverter  module  has 
short-circuited. 
 
Figure 6-2.1: Inverter module terminals