Part 
6
 
-
 
Diagnosis and Troubleshooting
 
Compressor discharge pipe temperature 
sensor does not be properly connected 
to outdoor main PCB.
1
 
Ensure the sensor are connected 
properly 
Compressor discharge pipe temperature 
sensor have short circuited or failed
2
 
Replace the faulty sensor 
High pressure sensor connection on 
outdoor main PCB is loose
3
 
Ensure the sensor is connected properly 
High pressure sensor has short-circuited 
or failed
4
 
Check the fault that EEVA in MS can not 
be fully closed. Or check the fault that 
expansion valve of IDU can not be fully 
closed or the fan does not work, which 
may result in partial evaporation. 
T6B-T6A<3°C and T6A-Te <3°C and EEVC 
minimum opening? 
T8 -Te <2°C and EEVA minimum 
opening(Evaporator)? 
Check the fault that EEVA or EEVC can’t 
be completely closed; or SV5 can’t be 
opened. 
Discharge part of the refrigerant. Add oil 
if it leaks during discharge 
Replace the outdoor main PCB 
 
Notes:   
1.  Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 on the outdoor main PCB.   
2.  Measure  sensor  resistance.  If  the  resistance  is  too  low,  the  sensor  has  short-circuited.  If  the  resistance  is  not  consistent  with  the  sensor’s  resistance 
characteristics table, the sensor has failed. 
3.  High pressure sensor connection is port CN17 on the outdoor main PCB. 
4.  Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor has 
failed. 
5.  Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher 
than normal.