Midea 
V6R
 Series Service Manual
 
2.28 A1w: Refrigerant leakage protection   
 Digital display output 
        
 Description 
  Refrigerant leakage protection.   
  All units stop running. 
  Error code is displayed on the unit with the error. 
 
 Trigger / recover condition 
  Trigger condition:   
If any MS reports refrigerant leak failure A1, the failure is sent to the ODU. 
The unit is stopped forcedly after the ODU reports A11. 
The unit is stopped forcedly 12 hours after the ODU reports A12. 
The unit is stopped forcedly 24 hours after the ODU reports A13. 
  Recover condition:   
The outdoor unit does not receive the refrigerant leakage fault signal sent by the MS. 
  Reset method: Resume automatically. 
 
 Possible causes 
  Refrigerant pipe or indoor unit leak. 
  The refrigerant leak sensor is not connected or has malfunction. 
  MS main control board is damaged. 
 
 Procedure 
 
Refrigerant pipe or indoor unit leak. 
Find leaks and repair welding 
The refrigerant leak sensor is not 
connected or has malfunction. 
Check the setting of dial S1 on the MS 
and whether the refrigerant sensor is 
connected properly and is not damaged