Diagnosis and Troubleshooting
 
Communication wires P Q have short 
circuited or disconnected
1
 
Reconnect the communication wires 
Wires between outdoor and MS 
communication terminals block are loose 
Ensure the wires are connected properly 
The sequence of the PQE signal lines is 
incorrect. 
Reverse the sequence of signal lines. 
Interference from high voltage (220V or 
higher) wires 
Ensure the communication wires and 
high voltage wires are separated 
Communication wires are close to a 
source of electromagnetic radiation such 
as transformer or strong fluorescent lamp 
Remove the source of interference, or 
add additional shielding to the 
communication wires 
The length of communication wire is over 
1200m 
Reduce the wire length to less than 
1200m 
Replace the outdoor main PCB or 
communication terminals block resolves 
the error 
Replace the MS PCB or communication 
terminals block 
 
Notes:   
1.  Measure the resistance among P, Q and E. The normal resistance between P and Q is 120Ω, between P and E is infinite, between Q and E is infinite.