2.33 U31, U32, U33: Stop valve is not open. 
 Digital display output 
         
 Description 
  U31: Liquid side stop valve is not opened. 
  U32: High pressure gas side stop valve is not opened. 
  U33: Low pressure gas side stop valve is not opened. 
  All units stop running. 
  Error code is only displayed on the master unit. 
 
 Trigger / recover condition 
  Trigger condition:   
U31: Pc_max ≥ 3.9MPa in heating operation. 
U32: Pc_max ≥ 3.9MPa in heating operation. 
U33: Pe_min < 0. 12MPa in cooling operation. 
  Recover condition:   
The stop valves are opened and system pressure recover to normal. 
  Reset method: Manually restart. 
 
 Possible causes 
  Stop valve is not open. 
 
 Procedure