20 Specification & Performance
4. Electric Characteristics
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Locked Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Output (KW)
Notes:
1. RLA is based on the following conditions, Indoor temp. 27℃ DB/19℃ WB, Outdoor temp. 35℃ DB
2. TOCA means the total value of each OC set.
3. MSC means the Max. current during the starting of compressor.
4. Voltage range. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not
below or above listed range limits.
5. Maximum allowable voltage variation between phases is 2%.
6. Selection wire size based on the value of MCA.
7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).