EasyManua.ls Logo

Midea V6-i Series - Wiring Diagrams

Midea V6-i Series
118 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V6-i VRF 50Hz
27
Part 2
-
Outdoor Unit
Engineering Data
Key components:
1. Oil separator:
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation
efficiency is up to 99%.
2. Accumulator:
Stores liquid refrigerant and oil to protect compressor from liquid hammering.
3. Electronic expansion valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
4. Four-way valve:
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the heat exchanger
functions as a condenser; when open, the heat exchanger functions as an evaporator.
5. Solenoid valve SV2:
Protects the compressor. If compressor discharge temperature rises above 98°C, SV2 opens and sprays a small amount
of liquid refrigerant to cool the compressor. SV2 closes again once the discharge temperature has fallen below 85°C.
6. Solenoid valve SV4:
Returns oil to the compressor. Opens once the compressor has run for 200 seconds and closes 600 seconds later and
then opens for 3 minutes every 20 minutes.
7. Solenoid valve SV7:
Allows refrigerant return to the compressor directly. Opens when indoor air temperature is close to the set temperature
to avoid frequent compressor on/off.
8. High and low pressure switches:
Regulate system pressure. When system pressure rises above the upper limit or falls below the lower limit, the high or
low pressure switches turn off, stopping the compressor. After 5 minutes, the compressor restarts.

Other manuals for Midea V6-i Series

Related product manuals