V6-i VRF 50Hz
30
7 Functional Components and Safety Devices
Table 2-7.1: Functional components and safety devices
Item
7-12HP V6-i VRF
Compressor
Compressor discharge pipe
temperature sensor
50°C = 50
Crankcase heater
25W × 2
Fan motor
Safety thermostat
On
115°C
Off
-
System
High pressure switch
Off: 4.4 (±0.1) MPa
/ On: 3.2 (±0.1) MPa
Low pressure switch
Off: 0.05 (±0.05) MPa
/ On: 0.15 (±0.05) MPa
High pressure sensor
Output voltage (V) = 1.1603 × P + 0.5
(where P is the discharge pressure in MPa)
Heat exchanger temperature
sensor
25°C = 10
Outdoor ambient temperature
sensor
25°C = 10