VC Pro VRF 50/60Hz
29
Part 2 - Outdoor Unit Engineering Data
68-74HP
Table 2-1.10: 68-74HP specifications
HP
68
70
72
74
Model name
MVC-1915WV2GN1
MVC-1965WV2GN1
MVC-2020WV2GN1
MVC-2085WV2GN1
Combination type
30HP+22HP+16HP
28HP+26HP+16HP
28HP+28HP+16HP
30HP+28HP+16HP
Power supply
V/Ph/Hz
380-415V 3N~50/60HZ
Cooling
1
Capacity
kW
191.5
196.5
202.0
208.5
kBtu/h
654.1
671.1
689.9
712.2
Power input
kW
62.00
61.74
64.42
67.85
EER
3.09
3.18
3.14
3.07
Connected
indoor unit
Total capacity
50-130%
Maximum quantity
64
Compressor
Type
DC inverter
Quantity
5
Oil type
FV 50s
Start-up method
Soft start
Fan
Type
DC
Quantity
5
Motor output
kW
0.56×4+0.75
Static pressure
Pa
20 default;60 customization option
Airflow rate
m3/h
44400
51800
52800
Drive type
20 default;60 customization option
Refrigerant
Type
R410A
Factory charge
kg
19+13+11
19×2+11
Pipe
connections
2
Liquid pipe
mm
22.2
Gas pipe
mm
44.5
Sound pressure level
3
dB(A)
67
68
Net dimensions (W×H×D)
mm
(1585×1615×765)+
(1250×1615×765)+
(960×1615×765)
(1585×1615×765)×2+(960×1615×765)
Packed dimensions (W×H×D)
mm
(1650×1810×840)+
(1305×1790×820)+
(1025×1790×830)
(1650×1810×840)×2+(1025×1790×830)
Net weight
kg
338+278+197
338×2+197
Gross weight
kg
362+297+213
362×2+213
Ambient temp.
Cooling
o
C
-5 to 55
Notes:
1. Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Diameters given are those of the unit's accessories.
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.